User manual HONEYWELL NXL HVAC
DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual HONEYWELL NXL HVAC. We hope that this HONEYWELL NXL HVAC user guide will be useful to you.
You may also download the following manuals related to this product:
HONEYWELL NXL HVAC QUICK GUIDE (285 ko)
HONEYWELL NXL HVAC QUICK GUIDE (285 ko)
HONEYWELL NXL HVAC QUICK GUIDE (285 ko)
HONEYWELL NXL HVAC INSTALLATION INSTRUCTIONS (1494 ko)
Manual abstract: user guide HONEYWELL NXL HVAC
Detailed instructions for use are in the User's Guide.
[. . . ] NXL HVAC & COMPACT USER'S MANUAL
AT LEAST THE 11 FOLLOWING STEPS OF THE START-UP QUICK GUIDE MUST BE PERFORMED DURING THE INSTALLATION AND COMMISSIONING. IF ANY PROBLEMS OCCUR, PLEASE CONTACT YOUR LOCAL DISTRIBUTOR.
Start-up Quick Guide 1. Before taking any commissioning actions read carefully the safety instructions in Chapter 1. Before the mechanical installation, check the minimum clearances around the unit and check the ambient conditions in Chapter 5. [. . . ] The wizard helps you choose between four different operating modes, Standard, Fan, Pump and High Performance. Each mode has automatic parameter settings optimised for the mode in question. The programming wizard is started by pressing the Stop button for 5 seconds, when the drive is in stop mode. See the figure below for the procedure:
START-UP WIZARD
START
Honeywell
=Push the button
MODE
Honeywell
rpm n
Honeywell
I n (A)
Honeywell
DONE
Honeywell
+
rpm
A
+
+
ENTER reset
+
+
+
-
reset
ENTER
-
ENTER reset
-
-
ENTER reset
-
ENTER reset
1 Push 5 seconds
to activate (in stop mode)
2 Select the
**
mode. See table below!
3 Accept
4 Tune 5 Accept n(rpm)
6 Tune 7 Accept I(A)
M
Standard
0 50 Hz Hz 20 50 Hz Hz
3 s 20 s 5 s 1 s
3 s
I *1, 5
H
400 V* 400 V* 400 V* 400 V*
50 0= 0= Hz Ramp Coasting
20 I *1, 1 L s 5 s I *1, 1
L
Fan
Pump
20 50 Hz Hz 0 50 Hz Hz
High performance
1 IH *1, 8 s
0= Ai1 0-10V 50 0= 0= 0= Hz Ramp Coasting Ai1 0-10V ** 50 0= 1= 0= Hz Ramp Ramp Ai1 0-10V ** 0= 50 0= 0= Hz Ramp Coasting automatic Ai1 torque 0-10V boost
0= Not used 0= Not used 0= Not used 1=
0= Not used 0= Not used 0= Not used 0= Not used
I/O I/O I/O
NOTE!Startup Wizard resets all other parameters to factory defaults!
I/O
*In drives of 208V. . . 230V this value is 230V
** In NXL HVAC the default start function for Fan or Pump mode is 2 = Conditional Flying Start which is recommended start function with Trip Free Output Switching function enabled as standard.
Figure 7-3. See the Application manuals for detailed parameter descriptions.
Honeywell
Control Keypad
55(96)
7
7. 4 Navigation on the control keypad
The data on the control keypad are arranged in menus and submenus. The menus are used for example for the display and editing of measurement and control signals, parameter settings (chapter 7. 4. 2), reference values (Chapter 7. 4. 3) and fault displays (chapter 7. 4. 4).
Location
The first menu level consists of menus M1 to E7 and is called the Main menu. The user can navigate in the main menu using the Browser buttons up and down. The desired submenu can be entered from the main menu using the Menu buttons. When there still are pages to enter under the currently displayed menu or page, the last digit of the figure on the display is blinking and by pressing the Menu button right, you can reach the next menu level. From there you will be able to navigate your way up to the desired menu using the menu and browser buttons. More detailed descriptions of the menus you will find later in this Chapter.
7
56(96)
Control Keypad
Honeywell
READ Y STOP
READ Y STOP
I/O term
I/O term
READ Y STOP
READ Y STOP
READ Y STOP
I/O term
I/O term
I/O term
READ Y STOP
READ Y STOP
READ Y STOP
I/O term
I/O term
I/O term
READ Y STOP
READ Y STOP
READ Y STOP
I/O term
I/O term
I/O term
Browse
reset
enter
Press to reset
READ Y STOP
READ Y STOP
READ Y STOP
I/O term
I/O term
I/O term
enter
Change value
Browse
READ Y STOP
READ Y STOP
READ Y STOP
I/O term
I/O term
I/O term
enter
Change value
Browse
READ Y STOP
READ Y STOP
READ Y STOP
I/O term
I/O term
I/O term
No editing!
Hz
Figure 7-4. Keypad navigation chart
Honeywell
Menu functions
Code Menu
Monitoring menu
Control Keypad
57(96)
7
Min
V1. 1
Max
V1. 24
M1
Selections See chapter 7. 4. 1 for the monitoring values NXL HVAC P2. 1 = HVAC parameters P2. 1. 15 = Basic parameters NXL Compact P2. 1 = Basic parameters
P2. 2 = Input signals P2. 3 = Output signals P2. 4 = Drive control P2. 5 = Prohibit frequencies P2. 6 = Motor control P2. 7 = Protections P2. 8 = Autorestart P2. 9 = PID control P2. 10=Pump and fan control See the application manuals for detailed parameter lists P3. 1 = Selection of control place R3. 2 = Keypad reference P3. 3 = Keypad direction P3. 4 = Stop button activation P3. 5 = PID reference 1 P3. 6 = PID reference 2 Shows the active faults and their types Shows the fault history list S6. 3 = Copy parameters S6. 5 = Security S6. 6 = Keypad settings S6. 7 = Hardware settings S6. 8 = System info S6. 9 = AI mode S6. 10 = Fieldbus parameters Parameters are described in chapter 7. 4. 7 E7. 1 = Slot D E7. 2 = Slot E
P2
Parameter menu
P2. 1
P2. 10
K3
Keypad control menu
P3. 1
P3. 6
F4 H5
Active faults menu Fault history menu
S6
System menu
S6. 3
S6. 10
E7
Expander board menu
E7. 1
E7. 2
Table 7-1. Main menu functions
7
58(96)
Control Keypad
Honeywell
7. 4. 1
Monitoring menu (M1)
You can enter the Monitoring menu from the Main menu by pushing the Menu button right when the location indication M1 is visible on the display. How to browse through the monitored values is presented in Figure 7-5. The monitored signals carry the indication V#. # and they are listed in Table 7-2. Monitoring menu
Honeywell
Control Keypad
59(96)
7
Code V1. 1 V1. 2 V1. 3 V1. 4 V1. 5 V1. 6 V1. 7 V1. 8 V1. 9 V1. 10 V1. 11 V1. 12 V1. 13
Signal name
Output frequency Frequency reference Motor speed Motor current Motor torque Motor power Motor voltage DC-link voltage Unit temperature Analogue input 1 Analogue input 2 Analogue output current Analogue output current 1, expander board Analogue output current 2, expander board DIN1, DIN2, DIN3 DIE1, DIE2, DIE3 RO1 ROE1, ROE2, ROE3 DOE 1 PID Reference PID Actual value PID Error value PID Output Autochange outputs 1, 2, 3
Unit
Hz Hz rpm A % % V V ºC
ID
1 25 2 3 4 5 6 7 8 13 14 26 31
Description
Frequency to the motor Calculated motor speed Measured motor current Calculated actual torque/nominal torque of the motor Calculated actual power/nominal power of the motor Calculated motor voltage Measured DC-link voltage Heat sink temperature AI1 AI2 AO1
mA mA
V1. 14
mA
32 15 33 34 35 36 Digital input statuses I/O expander board: Digital input statuses Relay output 1 status I/O exp. board: Digital output 1 status In percent of the maximum process reference In percent of the maximum actual value In percent of the maximum error value In percent of the maximum output value Used only in Pump and Fan Cascade control Shows the current drive configuration mode selected with start-up wizard: 0 = No mode selected (Default) 1 = Standard 2 = Fan 3 = Pump 4 = High performance
V1. 15 V1. 16 V1. 17 V1. 18 V1. 19 V1. 20 V1. 21 V1. 22 V1. 23 V1. 24
% % % %
20 21 22 23 30
V1. 25
Mode
66
Table 7-2. Monitored signals
7
60(96)
Control Keypad
Honeywell
7. 4. 2
Parameter menu (P2)
Parameters are the way of conveying the commands of the user to the frequency converter. The parameter values can be edited by entering the Parameter Menu from the Main Menu when the location indication P2 is visible on the display. Push the Menu button right once to move into the Parameter Group Menu (G#). [. . . ] Overtemperature warning is issued when the heatsink temperature exceeds 85°C.
Correcting measures
Check loading. Check cables.
2
Overvoltage
Make the deceleration time longer.
3
Earth fault
Check motor cables and motor.
8
System fault
Reset the fault and restart. In case of temporary supply voltage break reset the fault and restart the frequency converter. Check motor cable and motor.
9
Undervoltage
11 13 14
Output phase supervision Frequency converter under temperature Frequency converter overtemperature
15 16
Motor stalled Motor overtemperature
Motor stall protection has tripped. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE HONEYWELL NXL HVAC
Click on "Download the user Manual" at the end of this Contract if you accept its terms, the downloading of the manual HONEYWELL NXL HVAC will begin.