LIQUID FLOW SWITCHES
SPECIFICATION DATA & MOUNTING INSTRUCTIONS
FEATURES
· · · Cost-effective flow switches for HVAC applications. [. . . ] They are suitable for monitoring flow in water, oil, cooling circuits, and lubrication systems. Data for other media must be determined empirically.
MODELS
Specification Flow medium Mounting Maximum pipe temperature Pressure Paddle material Lever Sensor body Housing dimensions Weight Approvals S6065A1003 non-aggressive liquid Rp 1" (ISO7/1) 120 °C 11 bar 1. 4401 yellow brass yellow brass 113 x 70 x 65 mm 850 g TÜV-approved S6065A2001 aggressive liquid Rp 1" (ISO7/1) 120 °C 30 bar 1. 4401 1. 4404 1. 4404 108 x 70 x 72 mm 850 g TÜV-approved
® U. S. · All rights reserved
EN0B-0314GE51 R01008
S6065A1003/2001 LIQUID FLOW SWITCHES
SWITCH-POINT ADJUSTMENT
The flow switch is factory-set to the min. To adjust the device to other levels, turn the adjustment screw clockwise. flow 3 3 (m /h) (m /h) 1" 1" 3. 6 0. 6 / 1. 0 2. 0 / 2. 1 1" 1-1/4" 6. 0 0. 8 / 1. 3 2. 8 / 3. 0 1" 1-1/2" 9. 0 1. 1 / 1. 7 3. 7 / 4. 0 1"+2" 2" 15. 0 2. 2 / 3. 1 5. 7 / 6. 1 1"+2" 2-1/2" 24. 0 2. 7 / 4. 0 6. 5 / 7. 0 1"+2"+3" 3" 36. 0 4. 3 / 6. 2 10. 7 / 11. 4 1"+2"+3" 4" 60. 0 11. 4 / 14. 7 27. 7 / 29. 0 1"+2"+3"+Z* 4" Z 60. 0 6. 1 / 8. 0 17. 3 / 18. 4 1"+2"+3" 5" 94. 0 22. 9 / 28. 4 53. 3 / 55. 6 1"+2"+3"+Z* 5" Z 94. 0 9. 3 / 12. 9 25. 2 / 26. 8 1"+2"+3" 6" 120. 0 35. 9 / 43. 1 81. 7 / 85. 1 1"+2"+3"+Z* 6" Z 120. 0 12. 3 / 16. 8 30. 6 / 32. 7 1"+2"+3 8" 240. 0 72. 6 / 85. 1 165. 7 / 172. 5 1"+2"+3"+Z* 8" Z 240. 0 38. 6 / 46. 5 90. 8 / 94. 2 *For models with the suffix "Z, " the longest paddle must be used to obtain the values indicated in this table. The Z = 8" paddle must be cut to the proper length to fit into the pipe without touching the inside.
NOTE: If the flow switch is used as a min. flow controller, another device must be installed downstream for alarm condition activation.
DIMENSIONS
70 mm 135 mm 113 mm 65 mm 126 mm
paddles (L)
pipe Ø
rec. Qmax (m3/h)
reset / switch point
PG11 54 mm
R1"
1" 2" 3"
29 mm
Fig. [. . . ] La Pièce 16, Switzerland by its Authorized Representative: