[. . . ] T8360
24 VOLT ROOM THERMOSTAT
PRODUCT SPECIFICATION SHEET
The T8360 low voltage room thermostat has S. P. S. T. [. . . ] (non-condensing) : CE mark, complying with standards EN60730-1 (1995), EN55014-1 (1997), EN55014-2 (1996). : T8360A1000
o o o o
Performance
Switch life Environmental requirements
Approvals
Ordering Specification
DIMENSIONS
EN0R8538 R0 2004
2
T8360 24 VOLT ROOM THERMOSTAT
INSTALLATION
IMPORTANT 1. Disconnect the power supply before beginning installation
Mounting the thermostat
The T8360 can be mounted directly on the wall or on a conduit box (see Fig. An additional wall-plate is available for special mounting requirements.
Location
A T8360 room thermostat is the temperature control element in your heating system and must be located in a position with good air circulation at average temperature - on an inside wall about 1. 5 m above the floor. Do not position the thermostat in draughts, near hot or cold air from water pipes or radiant heat from the sun or appliances.
Wiring the thermostat
The standard wiring access is via a hole in the base of the thermostat, near the top edge. There are also 4 breakouts on the cover (2 on top and 2 on the sides) for surface wiring requirements.
Wall box mounting
Surface mounting Use wall box fixing holes or alternatives shown
screws supplied
screws supplied
Fig. 2 Mounting the Thermostat
OPERATION
Sensing Element
The thermostat sensing element comprises two circular, flexible metal plates welded together at the rims encapsulating a small quantity of gas in liquid form, whose pressure changes greatly in response to small variations in temperature. In effect, this dual diaphragm forms a 'bellows' which expands/contracts in sympathy with the ambient temperature changes - this movement serving to operate a snap acting switch rated to control the heating or cooling circuit.
Disposal of Thermostat
The thermostat contains no user serviceable parts. Please ensure product disposal is in a safe and environmentally friendly manner, in compliance with local regulations. [. . . ] If this is done, loads from 10 to 500mA can be switched.
3
EN0R8538 R0 2004
T8360 24 VOLT ROOM THERMOSTAT
WIRING
SERIES ANTICIPATOR : LOADS 90 130mA
24 V T8360A1000
90 130mA 3 2 1
HEATING LOAD
18R
NO ANTICIPATOR : LOADS 10 500mA
24 V T8360A1000
10 500mA 3 2 1
HEATING LOAD
Honeywell Control Systems Limited Newhouse Industrial Estate Motherwell ML1 5SB United Kingdom
EN0R8538 R0 2004
http://europe. hbc. honeywell. com [. . . ]