If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual TOSHIBA SATELLITE L870-198. We hope that this TOSHIBA SATELLITE L870-198 user guide will be useful to you.
Manual abstract: user guide TOSHIBA SATELLITE L870-198
Detailed instructions for use are in the User's Guide.
[. . . ] 8 7 Trial Operation Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
TCS-NET Relay Interface
Installation Manual
1
Precautions for Safety
· Read these "Precautions for Safety" carefully before installation. · The precautions described below include important items regarding safety. · After the installation work, perform a trial operation to check for any problem. [. . . ] · After the installation work, perform a trial operation to check for any problem. Ask the customer to keep this Installation Manual.
WARNING
· Ask an authorized dealer or qualified installation professional to install or reinstall the TCB-IFMB640TLE. · Turn off the main power supply switch or breaker before attempting any electrical work. · Perform installation work properly according to this Installation Manual. Any modification may cause a malfunction, resulting in overheating or fire.
CAUTION
· Perform wiring correctly in accordance with the specified the current capacity. · Connect the specified cables for the terminals securely to prevent external forces from affecting them. Failure to do so may result in disconnection, overheating, or fire.
2 (EN)
TCS-NET Relay Interface
Installation Manual
2
Introduction
Applications/Functions/Specifications
Applications
· The TCS-NET Relay Interface is used to connect air conditioners (with TCC-LINK installed) to the air conditioner control system or BACnet system.
Functions
· The TCS-NET Relay Interface converts signals between TCC-LINK and RS-485.
Specifications
Power supply Current Power consumption Operating temperature/humidity Storage temperature Chassis material Dimensions Mass 220 - 240 VAC, 50/60 Hz 18 mA 2. 4 W 0 to 40 °C, 10 to 90% RH (no condensation) -20 to +60 °C Galvanized sheet metal 0. 8t (no coating) 66 (H) x 170 (W) x 200 (D) mm 1 kg
External View
200
1 2 22 78 6- 5. 5 mounting holes 78 22 66 63. 6
3 4 147 Bottom side 156 170
5
22
78
78
22
Parts name 1 2 3 4 5 Case Case lid Grommet Grommet Grommet for power supply
Specifications Galvanized sheet metal Galvanized sheet metal C30-SG20A C30-SG20A C30-SG20A
3 (EN)
Top side
TCS-NET Relay Interface
Installation Manual
3
No. 1 2 3 4
Before Installation
Item TCS-NET Relay Interface Installation Manual Screw Leaflet (Caution for exchanging product) Quantity 1 1 4 1 M4 x 12mm tapping screws Remarks
Check the following package contents.
Use the following wiring materials to connect the signal lines and power lines. Line Type 1 For TCC-LINK Wire size Length Type 2 For RS-485 Wire size Length 3 For power Type Wire size Description 2-core shield wires 1. 25 mm2, 1000m max. (total length including air conditioner area) 2-core shield wires 1. 25 mm2, 500m max. Push the reset switch SW7 after changing the address.
7 (EN)
Remote controller
CAUTION: RS-485 signals A and B have polarity. Be careful when connecting the RS-485 wires.
Central remote controller
The shield of RS-485 cable should be open and insulated. It is not connected to the terminal block.
1
Indoor unit
Outdoor unit
Remote controller
Crimp 3 wires with a closed end wire joint.
Power supply
Indoor unit
NL
Central remote controller
SW5
RS-485
Red/Orange
A
B A U2 U1 FG
TCC-LINK
Connect the shield wires of the two wires.
SW6
SW1
8
Indoor unit
Indoor unit
NL
TCS-NET Relay Interface
Installation Manual
6
Setting
The following settings are necessary to use TCS-NET Relay Interface. · SW1 TCS-NET Relay Interface address set switch When two or more TCS-NET Relay Interface are used, set a different address for SW1 to avoid address duplication. Assign addresses in an ascending order.
CAUTION
· Set relay interface addresses according to the air conditioner address table. For the relay interface whose address SW1=1, perform terminator resistor setting. · When the SW1 setting has been changed, push the reset switch SW7. The new address setting is read.
· SW2 · SW3 · SW4
· SW5
· SW6 Test switch Test switch Test switch · SW7 Not used during operation. RS-485 terminator resistor select switch Set "Resistor set (120 ohm)" only when the relay interface address SW=1, and set "open" for other relay interfaces.
SW1
SW4
TCC-LINK terminator resistor select switch The TCC-LINK terminator resistor is set on the air conditioner side. Reset switch When performing an address setting with SW1, push this reset switch after the address setting to read the set value.
Relay interface address set switch 1-8 0, 9-F Relay interface address Not used
TCC-LINK U1 FG
2
ON
LED5
SW6
LED4
ON
1
SW3
SW2 SW3 SW4 SW5
Test switch (0 usually) Test switch (all OFF usually) Test switch RS-485 terminator resistor select switch
ON ON
U2
LED3
1
2
4
3
RS-485 B A
SW7
LED2
LED1
SW1
SW2
ON
SW5
1 2 3 4 1 2 3 4
1
2
3
4
Resistor Set SW6
Open
Bit1: pull-up resistor select. [. . . ] The new address setting is read.
· SW2 · SW3 · SW4
· SW5
· SW6 Test switch Test switch Test switch · SW7 Not used during operation. RS-485 terminator resistor select switch Set "Resistor set (120 ohm)" only when the relay interface address SW=1, and set "open" for other relay interfaces.
SW1
SW4
TCC-LINK terminator resistor select switch The TCC-LINK terminator resistor is set on the air conditioner side. Reset switch When performing an address setting with SW1, push this reset switch after the address setting to read the set value.
Relay interface address set switch 1-8 0, 9-F Relay interface address Not used
TCC-LINK U1 FG
2
ON
LED5
SW6
LED4
ON
1
SW3
SW2 SW3 SW4 SW5
Test switch (0 usually) Test switch (all OFF usually) Test switch RS-485 terminator resistor select switch
ON ON
U2
LED3
1
2
4
3
RS-485 B A
SW7
LED2
LED1
SW1
SW2
ON
SW5
1 2 3 4 1 2 3 4
1
2
3
4
Resistor Set SW6
Open
Bit1: pull-up resistor select. Bit4: terminator resistor select.
TCC-LINK terminator resistor select switch
ON ON
L
Note:Bit 2 is not used.
1 2 1 2
N
100 ohm SW7 Reset switch LED1 Power indicator
Open
LED2 RS-485 communication status indicator LED3 TCC-LINK Communication status indicator LED4 TCC-LINK Communication error indicator LED5 Test indicator
REQUIREMENT · RS-485 terminator resistor select switch SW5. [. . . ]